EasyManuals Logo
Home>gefran>Inverter>BDI50 Series

gefran BDI50 Series User Manual

gefran BDI50 Series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
3-11
3.3 Wiring Guidelines
3.3.1 Main considerations
1 Tightening Torque for Screw terminalsRefer to the tables 3-1, when using a
screwdriver or any other suitable tools to make connections.
2 Power terminals:
Single phase : L1 (L), L3 (N)
Three-phase 200V models: L1 (L), L2, L3 (N)
400V models: L1, L2, L3
3 For all cabling use copper wires and the cable size shall be according to the table
below rated at 40 degrees Celsius.
4 Power & Control cable Minimum rated voltage
240V AC system, 300V AC.
480V AC system, 600V AC.
5 Control cables should be separated from the power cables. Do not place them in the
same cable tray or cable trunking to prevent against electrical interference.
Table 3-1
Size
TM1
TM2
Cable Size
Tightening torque
Cable Size
Tightening torque
AWG
mm²
kgf.cm
Ibf.in
Nm
AWG
mm²
kgf.cm
Ibf.in
Nm
Size 1
22~10
0.34~6
14
12.15
1.37
24~12 0.5~2.5 4.08 3.54 0.4
Size 2
12.24
10.62
1.2
Size 3
18~8
0.82~8.4
18
15.58
1.76
24~12 0.5~2.5 5.1 4.43 0.5
Size 4
14~6
2~13.3
24.48
21.24
2.4
6 The maximum RMS symmetrical Current Ratings and voltage are listed as below:
Device Rating
Short circuit Rating Maximum Voltage
voltage
HP
220V 0.2~10 5000A 240V
440V 1~15 5000A 480V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran BDI50 Series and is the answer not in the manual?

gefran BDI50 Series Specifications

General IconGeneral
Brandgefran
ModelBDI50 Series
CategoryInverter
LanguageEnglish

Related product manuals