App 3-21
4. BACnet Specifications
Inverter BDI50 model is built-in standard BACnet MS/TP communication protocol structure to
meet the demand of automatic communication equipment. Control or monitor BDI50 via
BACnet to be allowable to read and modify specific parameter. BDI50 includes the
following supports of standard objects:
■ Inverter Objects
■ Analog Input ■ Analog Output ■ Analog Value
■ Digital Input ■ Digital Output ■ Digital Value
Refer to Table 3.1 for BDI50 supporting the property information of object classification. User
can collect related properties of objects required via the dedicated communication software
of BACnet to give control or monitor command for each object.
Table 3.1 Object and property supporting list
Property
Inverter
(DEV)
Analog
Input
(AI)
Analog
Output
(AO)
Analog
Value
(AV)
Digital
Input
(BI)
Digital
Output
(BO)
Digital
Value
(BV)
Object_Identifier
V
V
V
V
V
V
V
Object_Name
V
V
V
V
V
V
V
Object_Type
V
V
V
V
V
V
V
System_Status
V
Vendor_Name
V
Vendor_ Identifier
V
Model_Name
V
Firmware_Revision
V
Applocation_Software_Supported
V
Protocol_Version
V
Protocol_Revision
V
Protocol_Services_Supported
V
Protocol_Object_Type_Supported
V
Object_List
V
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_Of_APDU_Retries
Max_Masters
V
Max_Info_Frames
V
Device_Address_Binding
Location
V
Presnent_Value
V
V
V
V
V
V
Status_Flags

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran BDI50 Series and is the answer not in the manual?

gefran BDI50 Series Specifications

General IconGeneral
Brandgefran
ModelBDI50 Series
CategoryInverter
LanguageEnglish

Related product manuals