4-23
Group 13 Inspection & Maintenance functions
No. Description Range
Factory
Setting
unit Note
13-00
Drive Horsepower
Code
---- - - *3
13-01
Software Version
----
-
-
*3*4
13-02
Fault Log
(Last 3 Faults)
---- - - *3*4
13-03
Accumulated Operation
Time1 1
0~23 - hour *3
13-04
Accumulated Operation
Time1 2
0~65535 ---- day *3
13-05
Accumulated Operation
Time Mode
0:Time Under Power
1:Run Mode Time Only
0 - *3
13-06
Parameter Lock
0: Enable all Functions
1: Preset speeds 05-01~05-08 cannot
be changed
2: All Functions cannot be changed
Except for Preset speeds
05-01~05-08
3: Disable All Function
0 -
13-07
Parameter Lock Code
00000~65535
00000
-
13-08
Restore Factory
Settings
1150: Reset to factory setting.
(50Hz,220V/380V)
1160: Reset to factory setting.
(60Hz,220V/380V)
1250: Reset to factory setting.
(50Hz,230V/400V)
1260: Reset to factory setting.
(60Hz,230V/460V)
1350: Reset to factory setting.
(50Hz,220V/415V)
1360: Reset to factory setting.
(60Hz,230V/400V)
1250/1360
(*)
-
(*) Notes:
For built-in EMC filter models, the default setting of 13-08 is “1250”.
For without built-in EMC filter models, the default setting of 13-08 is “1360”