GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
15
5 ELECTRICAL PARAMETERS
Model
Power Supply
Fuse Capacity
Minimum Circuit
Ampacity
Maximum Overcurrent
Protection
V/Ph/Hz
A
A
A
GMV-72WM/B-F(U)
208V/230V 3~ 60Hz
45
30
45
GMV-96WM/B-F(U)
208V/230V 3~ 60Hz
70
45
70
GMV-120WM/B-F(U)
208V/230V 3~ 60Hz
100
74
100
GMV-144WM/B-F(U)
208V/230V 3~ 60Hz
70
55
70
GMV-168WM/B-F(U)
208V/230V 3~ 60Hz
90
70
90
GMV-192WM/B-F(U)
208V/230V 3~ 60Hz
125
99
125
GMV-216WM/B-F(U)
208V/230V 3~ 60Hz
125
111
125
GMV-240WM/B-F(U)
208V/230V 3~ 60Hz
150
140
150
GMV-264WM/B-F(U)
208V/230V 3~ 60Hz
150
123
150
GMV-288WM/B-F(U)
208V/230V 3~ 60Hz
150
136
150
GMV-312WM/B-F(U)
208V/230V 3~ 60Hz
175
164
175
GMV-336WM/B-F(U)
208V/230V 3~ 60Hz
200
177
200
GMV-360WM/B-F(U)
208V/230V 3~ 60Hz
225
205
225
Power cable wire gauge and circuit breaker must be selected based on the above parameters
and in compliance with local safety requirements. If there is conflict between above parameters and
national requirements, please contact the manufacture promptly.
If power cable wire gauge and circuit breaker is out of the above design range, fire hazard may
occur.

Table of Contents

Other manuals for Gree GMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5 Series and is the answer not in the manual?

Gree GMV5 Series Specifications

General IconGeneral
BrandGree
ModelGMV5 Series
CategoryInverter
LanguageEnglish

Related product manuals