GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
57
6 PIPE INSTALLATION AND INSULATION
6.1 PIPE INSTALLATION FOR THE COOLING SYSTEM
6.1.1 Precautions on Pipe Direction Design
Refrigerant pipe layout must be designed in accordance with the following principles:
1
The air conditioning installation should not damage the bearing structure or the decorative style.
Air conditioning pipes should be laid out along the bottom of beam as possible. If pipes meet one
another at the same elevation, process based on the following principles:
1
Drain pipes enjoy the highest priority. Air ducts and pressure pipes should leave places for
gravity pipes.
2
Air ducts and small pipes should leave places for major pipes.
2
The refrigerant pipe layout must be optimal in actual engineering with minimum pipe length and
bends. In this way, the performance of the unit can be maximized.
3
The refrigerant pipe cannot affect air discharge and return of internal units. The minimum
distance between the refrigerant pipe with an insulation layer and the air return box is 300 mm(11.8inch).
If the air return or manhole is at the right lower part of the unit, the minimum distance is 150 mm(5.9inch).
When the refrigerant pipe needs to be laid at the air outlet side, avoid laying the pipe at the front of the
air outlet. The refrigerant pipe cannot connect to any part of the unit except the joint points. If the
preceding principles are not followed, performance of the unit will be affected and running noises will be
increased.
4
The refrigerant pipe must be laid away from the manhole of the unit so that sufficient space can
be reserved for maintenance.
5
The riser should be installed in the air conditioning tube well, and the horizontal pipe should be
placed in the ceiling, if possible.

Table of Contents

Other manuals for Gree GMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5 Series and is the answer not in the manual?

Gree GMV5 Series Specifications

General IconGeneral
BrandGree
ModelGMV5 Series
CategoryInverter
LanguageEnglish

Related product manuals