Lynx Plus Series Installation and Setup Guide
- 75 -
UL NOTICES
1. For UL Residential Burglar Alarm installations with line security, total exit delay time must
not exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit
delay time must not exceed 120 seconds.
2. Periodic testing (see scheduling mode) must be at least every 24 hours.
3. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL
installations (Aux power 500mA max.).
4. Remote downloading without an alarm company technician on-site (unattended
downloading) is not permissible for UL installations.
5. Auto-disarming is not a UL Listed feature.
6. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial
and residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a
signal to a remote monitoring location, or to delay the energizing of a local alarm sounding
device to permit the alarm system user to enter and disarm the system, or to arm the system
and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring
location.
SIA Quick Reference Guide
1. *31 Single Alarm Sounding per Zone: If 0 selected, alarm sounding per zone will be the
same as the number of reports in armed period set in field *92 (1 if 1 report, 2 if 2 reports).
2. *34 Exit Delay: Options include 45-96 and 120 seconds. Minimum exit delay is 45 seconds.
3. *35/*36 Entry Delay 1 and 2: Options include 30-96, 120, 180, and 240 seconds. Minimum
entry delay is 30 seconds. When added together the entry delay plus the dialer delay should
not exceed 1 minute.
4. *39 Cross Zone Timer: Options include No cross zoning or selections between 15 seconds and
3 minutes, 45 seconds (in 15 second increments). Default is 0 no cross zoning
5. *40 PABX Access Code/Call Waiting Disable: If call waiting is used, call waiting cancel
option in field *47 must be set.
6. *47 Phone system Select: If call waiting is used, Call Waiting Disable must be enabled.
7. *50 Burglary Abort Window: Options include 15, 30 and 45 seconds. Delay must be a
minimum of 15 seconds.
8. *57 False Alarm Options: Default is 7 cancel alarm display, auto stay arming and exit time
restart/reset enabled.
9. *59 Exit Error Alarm Report Code: Always enabled.
10 *68 Cancel Report Code: Default is code enabled.
11. *69 Recent Closing Report Code: Always enabled.
12. *92 Swinger Shutdown: Default is 1 shutdown after one trip.

Table of Contents

Other manuals for Honeywell Lynx Plus Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Lynx Plus Series and is the answer not in the manual?

Honeywell Lynx Plus Series Specifications

General IconGeneral
BrandHoneywell
ModelLynx Plus Series
CategorySecurity System
LanguageEnglish

Related product manuals