Specifications 58
Specification 2450W Platinum Hot Plug
2650W Platinum Hot Plug
Input requirements
Rated input voltage
200 VAC to 208 VAC line to line
3-phase delta
200 VAC to 208 VAC line to line
3-phase delta
Maximum input current per
22 A at 208 VAC
24 A at 208 VAC
Maximum input power per
Three-phase power (International)
Redundant Power Supply
Redundant Power Supply
Power cords (2)
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
Input requirements
Rated input voltage
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
Maximum input current per
line cord
11.2 A at 240/415 VAC
12 A at 240/415 VAC
Maximum input power per
*Rated 220 VAC to 240 VAC line-to-neutral. The enclosure does not operate from higher line-to-line voltage with the
WYE wall plug configuration. Input AC modules are configured to provide 220 VAC to 240 VAC to the power supplies