FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
2 Routine Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
35
Maintenance
Item
Maintenance
Period
Operation
Standard
Troubleshooti
ng
intervals, the
communication
is interrupted.
s cable or WiFi
converter.
2.6.10 Routine Maintenance for the AC Actuator
Table 2-24 Routine maintenance for the AC actuator
Maintenance
Item
Maintenance
Period
Operation
Standard
Troubleshooti
ng
Check the
indicator on the
AC actuator.
Quarterly
Observe the
PWR, RUN,
and ALM
indicators.
If the green
PWR
indicator is
steady on,
the power
input is
normal.
If the RUN
indicator is
off, the
power is
abnormal. If
the RUN
indicator
blinks
slowly, the
multi-functi
onal sensor
is running
normally. If
the RUN
indicator
blinks at
short
intervals,
the
communicat
ion is
interrupted.
The ALM
indicator is
off.
If the PWR
indicator is
off, check
whether the
power cable
of the AC
actuator is
normal or is
properly
connected to
the front
end. If not,
reconnect
the cable. If
so, replace
the AC
actuator.
If the RUN
indicator
blinks at
short
intervals,
check
whether the
antenna is
shielded. If
so, install
the antenna
to a
different
position. If
not, replace
the antenna.
If the ALM
indicator is
steady on,
clear the
alarm by

Table of Contents

Other manuals for Huawei V100R001

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei V100R001 and is the answer not in the manual?

Huawei V100R001 Specifications

General IconGeneral
BrandHuawei
ModelV100R001
CategoryWireless Router
LanguageEnglish

Related product manuals