FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
2 Routine Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
47
Maintenance
Item
Maintenance
Period
Operation
Standard
Troubleshooti
ng
interrupted.
The ALM
indicator is
off.
ions cable is
loose or
disconnecte
d or whether
the smart
ETH
gateway is
energized.
If the ALM
indicator is
steady on,
clear the
alarm by
referring to
ECC800
Alarm
Reference
V100R001.
Check the
availability of
the rack
environment
unit.
Semi-annually
On the WebUI
of the ECC800,
choose
Monitoring >
IT Cabinet >
Rack
Environment
Unit to enter
the operating
information
page, and check
the
communication
status and
temperature.
The
communication,
temperature,
and door status
information of
the rack
environment
unit are
normally
displayed on
the WebUI of
the ECC800.
If the displayed
information is
not normal,
check whether
the
communication
s cable is loose
or
disconnected. If
so, reconnect
the cable. If not,
replace the rack
environment
unit.
2.7 Routine Maintenance for the Fire Extinguishing
System
2.7.1 Routine Maintenance for Smoke Detectors
Table 2-40 Routine maintenance for smoke detectors
Maintena
nce Item
Mainte
nance
Period
Operation
Expected
Result
Troubleshooting
Smoke
Quarterl
Check whether
The indicator
If the indicator blinks twice

Table of Contents

Other manuals for Huawei V100R001

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei V100R001 and is the answer not in the manual?

Huawei V100R001 Specifications

General IconGeneral
BrandHuawei
ModelV100R001
CategoryWireless Router
LanguageEnglish

Related product manuals