- 137 -
DC brake current at
stop
Factory default
value
0%
F6-13
Setup range 0%~ 100%
DC brake time at
stop
Factory default
value
0.8s
F6-14
Setup range 0.0s~ 36.0s
DC brake beginning frequency at stop: During the acceleration to stop, when
it reaches this frequency, the DC brake process at stop begins.
DC brake waiting time at stop: Prior to the beginning of DC brake at stop, the
driver stops output and starts DC brake upon this delay. It is used to prevent
the over current fault caused by DC brake beginning when the speed is
relatively high.
DC brake current at stop: It refers to the added DC brake quantity. The higher
this value is, the better the DC brake effect is.
DC brake time at stop: It refers to the added time of the DC brake quantity.
When this value is zero, it indicates there is no DC brake process, and the
driver will stop according to the setup decoration to stop process.
Brake using ratio
Factory
default value
100%
F6-15
Setup range 0% ~ 100%
It is enabled for the driver with built-in brake unit. It can be used to adjust the
brake effect of the bake unit.
Group F7 Keyboard and Display
LCD language
selection
Factory default
value
0
0 Chinese
F7-00
Setup range
1 English
It is enabled for the LCD keyboard. It is used to select the character mode of
LCD display.