- 90 -
Weak
magnetism
adjustment
coefficient
Factory
default value
4
A0-04
Setup
range
0~1000
When A0-00 =“0”, calculate the weak magnetism directly, the actual output of
weak magnetism current is to multiply the theoretical value by weak magnetic
current coefficient(A0-01), the greater setup value is,the greater the weak
magnetic current will be, the better the dynamic effect will be. But it may
cause speed and current oscillation if it is too large.
When A0-00=1, adjust weak magnetism current automaticlly, get the required
minimum weakening current. Adjustment speed is determined by weak
magnetism adjustment coefficient (A0-04), the bigger setup value is, the
faster the adjustment will be.But it may be caused by speed and current
oscillation if it is too large.
Output phase
failure PWM
detection time
Factory
default
value
0
A0-05
Setup
range
0~63000
Determine the phase failure detection time, the value is equal to zero that
does not do output phase failure detection, it can automaticlly set up after
motor parameter tuning.
Group A1 PG Card Group
Reserved
Factory
default value
-
A1-00~
A1-01
Setup
range
-
Encoder
Installation
angle
Factory
default value
0°
A1-02
Setup
range
0.0°~359.9°
The unit is 0.1 °, it is automatically set after the motor parameter tuning.