About the Product
Installation and Removal
16 9831/0650-3 16
Figure 10.
A Distance from wall = 1,500mm B Air inlet
C Air outlet
Indoor installations
Generator Set Room
For the correct installation of a generator set in closed premises, the size of the room must allow:
• The regular operation of the generator set.
• Easy access to its components for maintenance and possible repairs.
• The possibility of installing the generator set using the available means of transport. The door through
which the generator set is brought in must be central, so that the set remains centred once it is inside,
and there is no need to move it to facilitate access.
• The existence of apertures that allow oil replacement.
• The installation of the exhaust pipe with the minimum possible number of pipe elbows.
• The layout of the control panel (if an automatic set) to be in a position that allows the operator to have
complete visibility over the instruments when operating it.
• Air vents to allow cool air inside and ducting to direct hot air out of the room.