Operation
Instruments
31 9831/0650-3 31
Figure 20.
Control Push-Buttons
Table 3.
This button places the module into its STOP/RESET mode. This will clear
any alarm conditions for which the triggering criteria have been removed. If
the engine is running and the module is put into STOP mode, the module
will automatically instruct the generator to unload (`Close Generator' and
`Delayed Load Output 1, 2, 3 & 4' become inactive (if used)). The fuel sup-
ply de-energises and the engine comes to a standstill. Should any form of
remote start signal be present while operating in this mode, a start will not
occur.
This button places the module into its AUTO MODE. This mode allows the
module to control the function of the generator automatically. The module
will monitor the remote start input and battery charge status and once a
start request is made, the set will be automatically started and placed on
load (`Close Generator' and `Delayed Load Output 1, 2, 3 & 4' become ac-
tive in order from lowest to highest (if used)). Upon removal of the starting
signal, the module will remove the load from the generator and shut the set
down observing the stop delay timer and cooling timer as necessary (`Close
Generator' and `Delayed Load Output 1, 2, 3 & 4' become inactive at once
(if used)). The module will then await the next start event.