8 Start-up
8.1 Conditions
DANGER
Lethal voltages are still present in the connections and cables of the device even after
the device has been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
1. The device is only permitted to be put into operation by a specialist.
2. Unauthorized persons must not be able to access the device.
WARNING
Risk of burning due to hot surface
Heat sinks become very hot during operation.
1. Never touch the heat sinks after starting up the device.
2. Wait until a cooling time of at least 10 minutes has elapsed before starting the cleaning process.
The device has been mounted and electrically installed.
The PV generator supplies a voltage above the configured start voltage.
1. Connect the grid voltage using the external circuit breakers.
2. Connect the PV generator using the DC isolator switch (0 > 1)
ð The device begins operation.
ð During initial start-up: Follow the instructions of the New Connection Wizard.
NOTE
A mobile terminal device with WIFI interface is required in order to put the device into
operation.
The following functions are only available via the WEB interface:
1. Initial start-up
2. Parameterization
3. Resetting the device to its factory defaults
NOTE
We recommend using an up-to-date Firefox or Chrome browser or the default browser that is available
on the mobile terminal devices to configure the device via the web interface.
8.2 Preconditions relating to standards
Attachment of safety label in accordance with UTE
C15-712-1
The code of practice UTE C15-712-1 requires that, upon connection to the
French low-voltage distribution network, a safety sticker showing a warning to
isolate both power sources when working on the device must be attached to
each device.
F Attach the provided safety sticker to the outside of the device housing where it is
clearly visible.
ATTENTION
Présence de deux
sources de tension
- Réseau de distribution
-Panneux photovoltaïques
Isoler les deux sources
avant toute intervention
Fig.41: Adhesive label
UTE_C15-712-1
8 | Start-up Manual
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3
KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3 KACO blueplanet 155 TL3
KACO blueplanet 165 TL3
Page 38
EN-US

Table of Contents

Other manuals for Kaco blueplanet 125 TL3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kaco blueplanet 125 TL3 and is the answer not in the manual?

Kaco blueplanet 125 TL3 Specifications

General IconGeneral
BrandKaco
Modelblueplanet 125 TL3
CategoryInverter
LanguageEnglish

Related product manuals