The name plate must be permanently attached to the product and must be in legible condition.
Any other or additional use is not considered proper or intended use and can lead to an annulment of the
product guarantee. This includes:
Use of a distribution system that is not described (grid type)
Use of sources other than PV-strings.
Mobile use
Use in rooms where there is a risk of explosion
Use in direct sunlight, rain or a storm or other harsh environmental conditions
Outdoor use in environmental conditions that exceed the limits stated in the technical specifications >En-
vironmental data.
Operation outside the specification intended by the manufacturer
Overvoltage on the DC connection of over 1,000 V
Device modification
Standalone mode
2.2 Protection features
The following monitoring and protection functions are integrated in the device:
RCMU (Residual Current Monitoring Unit)
Overvoltage conductor / varistor to protect the power semiconductors from high-energy transients on the
grid and generator sides.
Device temperature monitoring system
EMC filter to protect the inverter from high-frequency grid interference
Grid-side varistors grounded to earth to protect the product against burst and surge pulses
Anti-islanding detection according to the current standards.
Isolation detection / residual current monitoring and disconnection function to detect isolation faults
NOTE
If the device is connected, the overvoltage conductors / varistors contained in the device have an impact on the
electrical system insulation resistance test as per HD 60364-6 / IEC 60364-6 Low-voltage installations- Part 6:
Verification.
IEC 60364-6 6.4.3.3 describes two options for this case. The first option is to disconnect devices with an over-
voltage conductor or, if this is not practicable, then the test voltage can be reduced to 250V.
2 | Safety Manual
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3
Page 8
EN

Table of Contents

Other manuals for Kaco blueplanet 3.0 TL3 M2 WM OD IIG0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kaco blueplanet 3.0 TL3 M2 WM OD IIG0 and is the answer not in the manual?

Kaco blueplanet 3.0 TL3 M2 WM OD IIG0 Specifications

General IconGeneral
BrandKaco
Modelblueplanet 3.0 TL3 M2 WM OD IIG0
CategoryInverter
LanguageEnglish

Related product manuals