6.1.7 Description of Sy (System) - Parameter
Adr.
min max
default
0006h
1
-
1
2390
Sy. 6 Inverter address
With Sy.6 the address is adjusted under which the inverter is addressed by ÑCOMBIVISì or another control. The possible
values are between 0 and 239, the default value is 1. If several inverters are operated simulaneously on the bus, it is
absolutely necessary to assign different addresses, since otherwise communication problems arise because several
inverters may responded at the same time. The development info DIN 66019II protocol (C0.F5.01I-K001) contains
further information.
Adr.
min max
default
0002h
1
hex
-
99990000
Sy. 2 Inverter identifier
A unique number is assigned to each type of frequency inverter which identifies the hard- and software. This value is
used for example by COMBIVIS to load the correct configuration files. Sy.2 kann mit dem angezeigten Wert beschrieben
werden (z.B. zur Identifikation von Downloadlisten).
Adr.
min max
default
0003h
1
P-ID
-
255-255
Sy. 3 Power unit code
On the basis of the power circuit identification the control recognizes the used power circuit respectively a change of the
power circuit and adjusts certain parameters accordingly. To accept a new P-Id enter positive values (see chap. 9
ÑE.Puchì).
Adr.
min max
default
0007h
1
-
5
60
Sy. 7 Baud rate ext. bus
Following values are possible for the baudrate of the serial interface:
Parameter value Baudrate
0 1200 baud
1 2400 baud
2 4800 baud
3 (default) 9600 baud
4 19200 baud
5 38400 baud
6 55500 baud
If the value for the baudrate is changed over the serial interface, it can only be changed again by way of the keyboard
or after adapting the baudrate of the master, since no communication is possible in the case of different baudrates
between master and slave.
If problems occur during the data transmission, select a baudrate up to max. 38400 baud.