6
6
63
KEB COMBIVERT F5-M / S
Name: Basis
12.05.04
Section PageDate
© KEB Antriebstechnik, 2002
All Rights reserved
Chapter
Functional DesriptionMotor Data and Controller
ANTRIEBSTECHNIK
KEB Antriebstechnik
GmbH & Co. KG
Schneeberg
Made in
Germany
-Mot IP IM W.KI. ∞Ckg
Hz V
cos
/Y
1/min
UV
~Mot Hz Nm mm
FL
M
Br
I
Sp max
DK 160 L 4 F I /TW150
96/1632804/ 001
3 55 B 3 F 40 127
VDE 053 0
15,0 KW
ϕ
50 230/400
0,86
1455
230/400
350
49,5/28,5 A
IGR 05B 2500 Imp
5V D0/RS 6xTTL
dr.1
dr.0
dr.5
dr.4
dr.2
6.6 Motor Data and
Controller
Fig. 6.6.1 Example of a motor name plate
6.6.1 Motor Name Plate
The adjustment of the correct motor data is important for many inverter functions,
since calculations are derived from it, which the inverter requires to achieve the
best possible results in the control of Boost and slip compensation.
6.6.2 Motor Data DASM
Following parameters can be taken directly from the name plate of the three-phase
asynchronous motor (DASM) and entered:
- dr.0 DASM rated current 0,0...710,0 A (Star-/Delta-connection)
- dr.1 DASM rated speed 0...64000 rpm
- dr.2 DASM rated voltage 120...500 V (Star-/Delta-connection)
- dr.3 DASM rated power 0,35...400,00 kW
- dr.4 DASM power factor cos(phi) 0,50...1,00
- dr.5 DASM rated frequency 0,0...400 Hz
Parameter dr.0 and dr.2 must always be adjusted in accordance with the used connection
(star or delta). For the above motor name plate it means that it is 230 V / 49,5A for
delta connection and 400 V / 28,5 A for star connection. It doesnít matter that for
example the rated output voltage of the inverter is larger (e.g. Ñ87Hz-chracteristicì).
dr.3
Motor data from name plate
(dr.0...dr.5)