Functional DesriptionPositioning and Synchronous Control
With two limit switches and one reference point switch; approaching of the the reference
point switch against the preferred direction; reference point approach with approaching
the reference mark of the encoder.
ï Terminal X2A.14 = Limit switch right (di.19 = 32)
ï Terminal X2A.15 = Limit switch left (di.20 = 64)
ï Terminal X2A.11 = Reference point switch (di.12 = 67108864)
ï Terminal X2A.10 = Start Reference point approach (di.11 = 134217728)
ï Reference speed = -100 rpm with counter-clockwise rotation (PS.21=-100)
If the zero impulse is not be aprroached (PS.14 Bit 2 = off), only the reference point
switched is cleared and the drive is then stopped.
Example 3
Pic. 6.11.6.c Reference point approach example 3
t1
t2
t
t
t
1
0
v
0
X2A.15
X2A.14
X2A.11
Output position
(t0)
Position after reference
point approach
PS.14 Bit 3 = right
Limit switch left
Limit switch right
Vref = -100 rpm
Start
ref.-approach
Signal at X2A.15
Clear the reference
limit switch with
0.25* PS.21
turn back of
zero encoder
Signal at X2A.11
Reaching the reference
limit switch (t2)
Overtravelling of
reference point switch