EasyManuals Logo
Home>KEB>DC Drives>COMBIVERT F5 Series

KEB COMBIVERT F5 Series Installation Guideline

KEB COMBIVERT F5 Series
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
GB - 52
CP-Parameter
CP.34 Source of rotation direction
The source rotation setting and the mode of evaluating the rotation setting is defined
with this parameter (Enter-Parameter). With CP.34 one does not modify the rotation
source of the fixed frequencies (CP.19... 21).
Value Function
0/1 Only application mode
2 Setting by way of terminal strip forward/reverse; negative set values are set
to zero (factory setting)
3 Setting by way of terminal strip forward/reverse; the signs of the setpoint
values have no effect on the direction of rotation
4 Setting by way of terminal strip run/stop (X2A.14) and forward/reverse
(X2A.15); negative values are set to zero
5 Setting by way of terminal strip run/stop (X2A.14) and forward/reverse;
the signs of the setpoint values have no effect on the direction of rotation
6 Set value dependent, positive value - clockwise rotation; negative value
counterclockwise rotation; with set value „0“ it is switched into status
„Low speed“ (LS)
7 Set value dependent, positive value - clockwise rotation; clockwise rotation
is indicated
8/9 Only application mode
CP.35 AN1 Set value selection
The set value input 1 (AN1) at the F5-GENERAL control can be triggered by various
signal levels. In order to correctly evaluate the signal, this parameter must be adapted
to the signal source. At the F5-BASIC control the signal source may not be re-adjusted.
Value Reference signal
0 0...±10 V DC / Ri = 56 kOhm
1 0...+20 mA DC / Ri = 250 Ohm
2 4...20 mA DC / Ri = 250 Ohm

Other manuals for KEB COMBIVERT F5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 Series and is the answer not in the manual?

KEB COMBIVERT F5 Series Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5 Series
CategoryDC Drives
LanguageEnglish

Related product manuals