TP-6805 8/15 67Section 5 Troubleshooting
1
GM90211
1. Thermostat
Figure 5-6 Thermostat Location, 20RESB/RESD
1. Thermostat
2. Locations of nuts and screws that secure the front panel
GM93897
1
2
Figure 5-7 Thermostat Location, 20RESC/RESCL
5.8 OnCue Plus Troubleshooting
See the OnCuer Plus Operation Manual for
troubleshooting instructions for the OnCue Plus
Generator Management System.
5.9 Fuel System Troubleshooting
Most problems with gas fuels involve either fuel
pressure or fuel regulator function. Basic
troubleshooting consists of verifying fuel pressures and
checking each fuel system component.
Check the following items:
D Check primary fuel regulator outlet pressure. This is
the line pressure.
D Check the primary regulator vent for obstructions and
clean, if necessary.
D Check fuel shutoff inlet pressure.
D Check secondary fuel regulator inlet pressure.
D Check fuel inlet pressure at the gas mixer.
D Perform fuel system maintenance if necessary. See
Section 2.9, Fuel System Maintenance.