Appendix External switching of the
fuel control element
External switching of the If the output channels of the device are insufficient, it is possible to switch the
uel control element fuel control elements, which are not used in all curve sets (e.g. motor for oil
control element and motor for gas control element).
_____________________________________________________________
When an external switching of the fuel control element is used you have to
ensure, that the chosen motor matches the appropriate feedback
e.g. compulsory guide or equal methods.
_____________________________________________________________
For switching of the potentiometer it is necessary to use only contacts with
gold coating.
_____________________________________________________________
The cables between FMS and the relais modules may not exceed the length
of 10m!
_____________________________________________________________
Switching oil/gasmotor FMS
Relay modules
660R0013
or
660R0131
Feedback
FMS
Output
Oil
Gas
M
M
!
!
!
123

Table of Contents

Other manuals for Lamtec FMS 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS 4 and is the answer not in the manual?

Lamtec FMS 4 Specifications

General IconGeneral
BrandLamtec
ModelFMS 4
CategoryController
LanguageEnglish

Related product manuals