Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper
meter- design- level limit limit Standard
No. nation Description values Aids
_____________________________________________________________________________________________________
711 BandV K4 1 0 50 Band shift 4 P3
Channel 4
712 BandV K5 1 0 50 Band shift 4 P3
Channel 5
Compound
718 Laufz L 1 0 65535 Running time in pts./min for TPS 9999 P12
Load input
In the event of load via current or
pot, the value must be 0
719 Laufz K1 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 1
720 Laufz K2 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 2
721 Laufz K3 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 3
722 Laufz K4 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 4
723 Laufz K5 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 5
729 stopVERB 1 10 100 Minimum compound running time 10 P15
in seconds
730 minTAKT1 1 1 100 Minimum cycle length for channel 1 1 P16
in 20ths seconds per digit (50 ms)
731 minTAKT2 1 1 100 Minimum cycle length for channel 2 1 P16
in 20ths seconds per digit (50 ms)
732 minTAKT3 1 1 100 Minimum cycle length for channel 3 1 P16
in 20ths seconds per digit (50 ms)
733 minTAKT4 1 1 100 Minimum cycle length for channel 4 1 P16
in 20ths seconds per digit (50 ms)
734 minTAKT5 1 1 100 Minimum cycle length for channel 5 1 P16
in 20ths seconds per digit (50 ms)
740 PauseT1 1 1 100 Minimum pause between channel 1 cycles 2 P27
in 20ths seconds per digit (50 ms)
741 PauseT2 1 1 100 Minimum pause between channel 2 cycles 2 P27
in 20ths seconds per digit (50 ms)
742 PauseT3 1 1 100 Minimum pause between channel 3 cycles 2 P27
in 20ths seconds per digit (50 ms)
743 PauseT4 1 1 100 Minimum pause between channel 4 cycles 2 P27
in 20ths seconds per digit (50 ms)
744 PauseT5 1 1 100 Minimum pause between channel 5 cycles 2 P27
in 20ths seconds per digit (50 ms)
24

Table of Contents

Other manuals for Lamtec FMS 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS 4 and is the answer not in the manual?

Lamtec FMS 4 Specifications

General IconGeneral
BrandLamtec
ModelFMS 4
CategoryController
LanguageEnglish

Related product manuals