99
FMS Fault Correction Load signal (D)
Aids
D6
Load rating does not attain If the load transducer is in the maximum position but does not emit the
the highest value indicated highest possible value.
Make sure that this position of the load transducer is the highest
load rating position that occurs in operation.
_____________________________________________________________________________________________________
D7
Fault 320 Load input is not correctly connected
In the case of load due to current default:
Current is less than 4 mA, poles possible reversed
Check wiring
Check input current
_____________________________________________________________________________________________________
D11
Fault 372 The two load ratings for main and monitoring processor are compared with
one another.
Change processor card.
_____________________________________________________________________________________________________