7 Operating Control and Displays
7.1.4 Manual Menu Path
MANUELL
Select MANUAL path to carry out actions as follows:
• Switching burner ON and OFF
• Presetting of burner firing rate
NOTICE
At least release level1 is required to start the burner.
The ’Burner ON’ control loop does not need to be switched on to start the burner from this
menu. The user interface assumes control in this menu.
If there is no ’Burner ON’ signal from other sources (terminal X10.2) software switches off the
burner when you exit the menu.
CAUTION!
If you carry out a manual start-up via display CMS no longer responds to ’Burner ON’ signal
input at connector X10.2. Therefore that limiters, monitors and other similar safety functions
must not be operated with this input!
NOTICE
Leaving of window will terminate manual burner operation!
NOTICE
Changes of burner firing rate are possible only while burner is running.
If you want to adjust burner firing rate remember to start-up the burner first.
Start burner manually
Adjust burner firing rate