8 CO/O
2
Control
4 Tab ’Behaviour during optimisation’
5 Maximum firing rate difference for static optimisation
During static optimisation, the internal firing rate is frozen. As soon as the requested fir-
ing rate exceeds the set value, the optimisation is stopped and the firing rate adjustment
is enabled again. Value range 0 ... 999 digit.
6 Time [s] to cancel a completed optimisation while the burner is running
Validity of the optimisation points adjustment.
Time value to start a new optimisation after a successful completion in hours.
Value range = 0 ... 17780 s.
Each optimisation point is treated individually. The time begins to run as soon as the
optimisation in the affected firing rate segment has been completed.
Factory setting: 28800 8 h.
7 Burner down time [Min]: After expiry the CO optimisation is released immediately after
the start of the controller
Factory setting: 60 Min*
* i. e. If the burner remains switched OFF for longer than 60 Min, the CO control is ena-
bled immediately after burner ON in order to counteract an earlier formation of CO in a
cold combustion chamber.