73
4 CMS Components
NOTICE
The limits of the technical data must be strictly adhered to.
Environmental conditions
Operation Temperature range 0 - +55 °C (non-condensing)
Relative humidity Max. 85%, non-condensing
Transport Temperature range 20 - +70 °C (non-condensing)
Relative humidity Max. 85%, non-condensing
Storage Temperature range 20 - +70 °C (non-condensing)
Relative humidity Max. 85%, non-condensing
Electrical safety IP rating according to DIN EN 60529 IP20
IP54 front (IP65 only with tensioned twist lock)
Protection class III
Dielectric strength EN 61131-2
ESD resistance EN 61131-2
Electrostatic discharge EN 55011 class B, group 1
Mech. safety Vibration Sinusoidal (EN 90068-2-6)
Test: Fc; 10 - 150 Hz, 1 G (operating mode)
Shock resistance 15 G (approx. 150 m/s
2
), duration 10 ms, semi-
sinusoidal
(EN 6068-2-27)
Test: Ea
Certification:
CE EN 61131-2
CB Scheme IEC 61010-2-201
c
UL
us
UL 61010-2-201