Technical data
General data and operating conditions
4
l
27
EDS700ACBA EN 5.1
4 Technical data
4.1 General data and operating conditions
Conformity and approval
Conformity
CE
2006/95/EC Low−Voltage Directive
2004/108/EC EMC Directive
Machinery Directive 2006/42/EC Logic unit to ensure safety functions
(safety component acc. to Machinery Directive)
EAC
TP TC 004/2011
(TR CU 004/2011)
On safety of low voltage
equipment
Eurasian Conformity
TR CU: Technical
Regulation of Customs
Union
TP TC 020/2011
(TR CU 020/2011)
Electromagnetic compatibility of
technical means
Approval
C
UL
US
UL 508C
CSA 22.2 No. 14
E70ACxSE...
Industrial Control
Equipment, Lenze File
No. E132659
C
UR
US
E70ACxSC...
E70ACxSD
...
Protection of persons and devices
Enclosure
EN 60529
IP 20
Specification
l applies to the fully
assembled state ready
for use
l does not apply to the
wire range of the
terminals
UL Protection against contact in
accordance with Open Type
EN 60529 Mounting type "push−through technique", heatsink side:
l IP54
Insulation resistance EN 61800−5−1
< 2000 m amsl: overvoltage category III
> 2000 m amsl: overvoltage category II
Insulation of control
circuits
EN 61800−5−1 Safe mains isolation through double/reinforced insulation
(^ 6.1.1):
l Touch probe inputs
l Safety system inputs
l Encoder feedback (^ 56)
Short−circuit strength EN 61800−5−1 l Motor connection: limited, controller is inhibited, error
acknowledgement is required
l Brake control: limited, error acknowledgement is required
l Control electronics and holding brake supply connections:
not short−circuit−proof
Protective measures
integrated for
l Short circuit
l Earth fault
l Overvoltage
l Motor overload (temperature detection via encoder, I
2
t
monitoring)
Contact current EN 61800−5−1 > 3.5 mA AC, > 10 mA DC Observe the regulations
and safety instructions!
mains switching Cyclic mains switching of 5 times in 5 minutes is permissible
without restrictions.
Starting current £ 2 x I
rated
Discharge time of charge
stored after mains
disconnection
typically 5 min
The duration is indicated by a warning symbol on the device.

Table of Contents

Other manuals for Lenze i700 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i700 Series and is the answer not in the manual?

Lenze i700 Series Specifications

General IconGeneral
BrandLenze
Modeli700 Series
CategoryInverter
LanguageEnglish

Related product manuals