EasyManuals Logo
Home>Lenze>Inverter>i700 Series

Lenze i700 Series User Manual

Lenze i700 Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
Electrical installation
Important notes
Motor protection
6
l
88
EDS700ACBA EN 5.1
ƒ In case of condensation, do not connect the controller to the mains voltage before
the moisture has evaporated completely.
ƒ Provide unused control inputs and outputs with terminal strips.
6.1.3 Motor protection
ƒ Extensive protection against overload by means of temperature monitoring:
with KTY or PTC sensors of the resolvers or encoders
with activated I
2
t monitoring
Combination of the possible monitoring modes
ƒ Only use motors which have a suitable insulation for the inverter operation:
Insulation resistance: min. û = 1.5 kV, min. du/dt = 5 kV/ms
When using motors with an unknown insulation resistance, please contact your
motor supplier.
6.1.4 Interaction with compensation equipment
ƒ Drive control systems only consume very little fundamental reactive power from the
supplying AC system. Therefore, compensation is not required.
ƒ If the drive control systems are operated on supply systems by means of
compensation equipment, the compensation equipment must include chokes.
For this purpose, please contact the supplier of the compensation equipment.

Table of Contents

Other manuals for Lenze i700 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i700 Series and is the answer not in the manual?

Lenze i700 Series Specifications

General IconGeneral
BrandLenze
Modeli700 Series
CategoryInverter
LanguageEnglish

Related product manuals