Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
Motor cable
6
l
96
EDS700ACBA EN 5.1
6.3.3 Motor cable
ƒ Only use shielded motor cables with braids made of tinned or nickel−plated copper.
Shields made of steel braids are not suitable.
The overlap rate of the braid must be at least 70 % with an overlap angle of 90 °.
ƒ The cables used must correspond to the requirements at the location (e.g.
EN 60204−1).
ƒ Connect the shield with a large surface and fix it with metal cable binders or a
conductive clamp.
ƒ Connect the shield directly to the corresponding device shield sheet.
If required, additionally connect the shield to the conductive and earthed
mounting plate in the control cabinet.
ƒ The motor cable is optimally installed if
it is separated from mains cables and control cables,
it only crosses mains cables and control cables at right angles,
it is not interrupted.
ƒ If the motor cable must be opened all the same (e.g. due to chokes, contactors, or
terminals):
The unshielded cable ends may not be longer than 100 mm (depending on the
cable cross−section).
Install chokes, contactors, terminals etc. spatially separated from other
components (with a min. distance of 100 mm).
Install the shield of the motor cable directly before and behind the point of
separation to the mounting plate with a large surface.
ƒ Connect the shield with a large surface to PE in the terminal box of the motor at the
motor housing.
Metal EMC cable glands at the motor terminal box ensure a large surface
connection of the shield with the motor housing.
Motor supply cable Cable gland
Motor supply cable
max. 500mm
Large-surface
contact of
cable shield
Braid
Heat-shrinkable tube
Cable gland acc. to EMC with
high degree of protection
Cable gland
8200EMV023 8200EMV024
Fig. 6−2 Shielding of the motor cable

Table of Contents

Other manuals for Lenze i700 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i700 Series and is the answer not in the manual?

Lenze i700 Series Specifications

General IconGeneral
BrandLenze
Modeli700 Series
CategoryInverter
LanguageEnglish

Related product manuals