Doc# 100576 • REV C (Sept 2017) Page 30 of 42
5.2 MX2034 ONLY
Maximum current below
20 mA
Loop resistance too large or
power supply too low.
Verify that total loop resis-
tance does not exceed the
maximum per Installaon
Manual 100545.
Current output stuck < 3.5
mA
Probe is disconnected or out
of range
Verify that the probe is con-
nected and the gap is in the
specied OK region.
Current output high or low Incorrect 4 – 20 Scale
selected
Upload the device informa-
on (see Secon 3.5.2) and
verify the congured scale.