Installation
*INSTALLATION*
60
Steam connection (only for steam-heated variants)
The steam connection must only be carried out by an authorized in-
stallation technician. The enclosed installation instructions must be
observed as they are important for the steam connection.
Hot water connection (only for hot water-heated variants)
The hot water connection may only be carried out by an authorized in-
stallation technician.
The enclosed installation instructions must be observed as they are
important for the hot water connection.
If a faucet is desired, it must be installed on site.
Gas connection (only for gas-heated variants)
The gas connection must only be carried out by an authorized installa-
tion technician in accordance with the applicable national regulations
(see installation instructions).
The installation must conform with local codes or, in the absence of
local codes, with the National Fuel Gas Code, ANSIZ223.1/NFPA 54,
or the Natural Gas and Propane Installation Code, CSAB149.1
The dryer and its manually operated appliance main gas valve must be
disconnected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2psi (3.5kPa).
The dryer must be isolated from the gas supply piping system by clos-
ing the equipment shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than 1/2psi
(3.5kPa).
A minimum 1/8-in NPT plugged tapping, accessible for test gauge
connection, must be installed immediately upstream of the gas supply
connection to the dryer.
The use of a gas socket is not permitted at the specified heater rating
as the flow rate is too low.
The gas heating is configured at the factory in line with the gas specifi-
cations on the sticker on the rear of the machine.
If the gas type is changed, a conversion kit must be requested from
Miele Service (please specify the machine type, serial number, gas
type, gas group, gas connection pressure, and country of installation).
Follow the installation instructions. This conversion may only be car-
ried out by an authorized specialist.