3.2.3 LEV Assembly Design Capacity Range
The table below shows the design capacity for each LEV Assembly model.
NOTE
Two PAC-LV96AC-1 assemblies can be combined in parallel to achieve a design capacity
range of 120,000-192,000 Btu/h.
Two PAC-LV120AC-1 assemblies can be combined in parallel to achieve a design capacity
range of 192,000-240,000 Btu/h.
See section LEV Assembly installation for details on LEV Assembly installation.
LEV Assembly
Model
Design Capacity Range
[Btu/h]
Capacity Code
Setting [Ton]
LEV PAC-LV24AC-1 4,800 - 24,000 0.5, 0.7, 1, 1.25, 1.5, 2
LEV PAC-LV48AC-1 24,000 – 48,000 2.25, 2.5, 3, 4
LEV PAC-LV60AC-1 48,000 - 60,000 4.5, 5
LEV PAC-LV96AC-1 60,000 - 96,000 6, 8
LEV PAC-LV120AC-1 96,000 - 120,000 10
LEV PAC-LV96AC-1 (x2) 120,000 - 192,000 12, 14, 16
LEV PAC-LV120AC-1 (x2) 192,000 - 240,000 18, 20
PAC-AH001-1
17 © 2017 Mitsubishi Electric US, Inc.
ENGLISH