7.2.3 Connection for Operation with Third Party Controller
A 3rd party controller can be installed to control the following functions of the AHU controller:
ON/OFF (Operation) function
Temperature set point (Analog Input) function
The AHU controller can either be controlled by a Mitsubishi controller or a 3rd party controller; it cannot
be installed to be controlled by both.
Wiring for ON/OFF (Operation) function
Connection circuit
Operation contact specifications
SW1: Operation command
(field supply)
Minimum applicable load
DC5 V, 1 mA
Use a relay when the electrical wire exceeds 10 m.
X: Relay (field supply)
Minimum applicable load
DC5 V, 1 mA
SW1: Operation command
(field supply)
A1
A2
SW1
Maximum 10 m
SW2
A1
A2
X
X
Maximum 10 m
Relay
power
source
Wiring for temperature set point (Analog Input)
Connection circuit
Analog input
TBY Wiring: AWG22~26
B1 +DC0~10V
-
DC0~10V
B2
To operate the system using a 3rd party controller, connect the jumper connector “CNRM” located inside
the AHU controller as shown below. Connecting “CNRM” activates the control of the 3rd party controller.
Fig 7.2.3
PAC-AH001-1
35 © 2017 Mitsubishi Electric US, Inc.
ENGLISH

Table of Contents

Other manuals for Mitsubishi Electric CITY MULTI PAC-AH001-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric CITY MULTI PAC-AH001-1 and is the answer not in the manual?

Mitsubishi Electric CITY MULTI PAC-AH001-1 Specifications

General IconGeneral
BrandMitsubishi Electric
ModelCITY MULTI PAC-AH001-1
CategoryController
LanguageEnglish

Related product manuals