EasyManuals Logo

Mitsubishi City Multi PEFY-P72NMHSU-E User Manual

Mitsubishi City Multi PEFY-P72NMHSU-E
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
26- 26 -
HWE10170 GB
1. Error Code
Position detection error at startup (Indoor unit)
2. Error definition and error detection method
Position error is detected by the hall sensor at inverter startup.
3. Cause, Check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter.
(page 47)
1. Error Code
Position detection error during operation (Indoor unit)
2. Error definition and error detection method
Position error is detected by the hall sensor during operation.
3. Cause, Check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter.
(page 47)
4255
Cause Check method and remedy
(1) Loose connector Check the CNCT1 and CNINV connectors on the
INV board for proper connection.
(2) Inverter failure or fan motor error 1) Refer to [8] 3.2.[2].(page 48)
2) Refer to [8] 3.2.[3].(page 49)
4255
Cause Check method and remedy
(1) Loose connector Check the CNCT1 and CNINV connectors on the
INV board for proper connection.
(2) Inverter failure or fan motor error 1) Refer to [8] 3.2.[2].(page 48)
2) Refer to [8] 3.2.[3].(page 49)
HWE10170.book 26 ージ 2011年7月19日 火曜日 午後2時57分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi City Multi PEFY-P72NMHSU-E and is the answer not in the manual?

Mitsubishi City Multi PEFY-P72NMHSU-E Specifications

General IconGeneral
BrandMitsubishi
ModelCity Multi PEFY-P72NMHSU-E
CategoryAir Conditioner
LanguageEnglish