1. Error Code
Open-circuited IPM/Loose ACCT connector (Indoor unit)
2. Error definition and error detection method
ACCT sensor detected that not enough current is available.
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter.
(page 47)
1. Error Code
Loose float switch connector
2. Error definition and error detection method
Detection of the disconnected float switch (open-phase condition) during operation
3. Cause, check method and remedy
(1) CN4F disconnection or contact failure
Check for disconnection of the connector (CN4F) on the indoor controller board.
5305
Cause Check method and remedy
(1) Disconnected ACCT sensor Check CNCT2 on the INV board for proper connection.
(2) ACCT sensor fault Disconnect the CNCT2 connector, and check the resistance between
the terminals.
Refer to [8] 3.4.(page 50)
(3) Inverter failure or fan motor error 1) Refer to [8] 3.2.[2].(page 48)
2) Refer to [8] 3.2.[4].(page 49)
3) If no problems were found with items 1) and 2) above and the prob-
lem persists after resuming operation, replace the INV board and the
ACCT sensor.
4) If the problem persists after taking step 3) above, replace the fan mo-
tor.
5701
HWE10170.book 29 ージ 2011年7月19日 火曜日 午後2時57分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi City Multi PEFY-P72NMHSU-E and is the answer not in the manual?

Mitsubishi City Multi PEFY-P72NMHSU-E Specifications

General IconGeneral
BrandMitsubishi
ModelCity Multi PEFY-P72NMHSU-E
CategoryAir Conditioner
LanguageEnglish

Related product manuals