EasyManuals Logo
Home>Mitsubishi>Control Unit>FX2N

Mitsubishi FX2N User Manual

Mitsubishi FX2N
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #65 background imageLoading...
Page #65 background image
FX2N-32DP-IF Profibus-DP Interface Units Appendix B
B-11
B-4 Changing the High Speed Mode/Normal Mode
The user parameter settings are as shown in FX
2N
-4AD example. For FX
2N
-4DA, the settings
must correspond to their respective BFM locations. For definitions of the BFM’s, refer to each
modules user’s manual.
Table B-11:Changing the High Speed Mode/Normal Mode for FX
2N
-4AD
Using GSD File
User
Parameter
Type
Description
Using Programming Tool
Byte
No.
Setting
Value
(Hex)
Register
No.
Setting
Value
(Hex)
Higher/
Lower
Byte
0 00 H User
parameter
for 32DP-IF
See section 6.1. D200 0000 H
Lower
1 00 H Higher
2DA H
User
parameter
for special
function
block
(FX
2N
-4AD)
BFM #30 lower byte
D201 07DA H
Lower
3 07 H BFM #30 higher byte Higher
4 09 H
Total length of parameter bytes for this
special function block is 9 bytes (byte
No. 4 ~ 12).
D202 0409 H
Lower
5 04 H
Example: number of BFM for data
exchanged every cycle is 4
BFMs (BFM #9 ~ #12).
Higher
6 09 H Specified exchange, ex. BFM #9
D203 0A09 H
Lower
7 0A H Specified exchange, ex. BFM #10 Higher
8 0B H Specified exchange, ex. BFM #11
D204 0C0B H
Lower
9 0C H Specified exchange, ex. BFM #12 Higher
10 8F H
Example: Using high speed mode, BFM
#15 is set to “0001 H”.
D205 018F H
Lower
11 01 H BFM #15 lower byte: “01 H” Higher
12 00 H BFM #15 higher byte: “00 H”
D206 0000 H
Lower
- - - Higher

Table of Contents

Other manuals for Mitsubishi FX2N

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX2N and is the answer not in the manual?

Mitsubishi FX2N Specifications

General IconGeneral
BrandMitsubishi
ModelFX2N
CategoryControl Unit
LanguageEnglish

Related product manuals