43
VII.
Test Run by the Remote Controller (for Mr. SLIM P series)
LCD
Contents of inferior phenomena
P1~9
Fb
U1~UP
F3~F9
E0~E5
E6~EF
----
FFFF
Malfunction indoor unit
Malfunction indoor unit
Malfunction outdoor unit
Malfunction
outdoor unit
Remote controller transmitting error
Indoor/outdoor unit communication error
No error history
No applied unit
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
LED1
(microcomputer power supply)
LED2
(remote controller)
LED3
(indoor/outdoor communication)
Lits when power is supplied.
Lits when power is supplied for wired remote controller.
The indoor unit should be connected to the outdoor unit with address “0” setting.
Blink when indoor and outdoor unit are communicating.
Press the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD
display.For details,please refer to "VIII.2. Error code list".

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MA Series and is the answer not in the manual?

Mitsubishi MA Series Specifications

General IconGeneral
BrandMitsubishi
ModelMA Series
CategoryRemote Control
LanguageEnglish

Related product manuals