Temperature settings
F
or smooth, reliable operation, it is important that the temperature settings are correct.
The default settings are chosen for normal conditions, but it may be necessary to adjust them for the
specific installation.
Ventilation
Temperature regulation
↳
Desired room temperature (°C) Settings:
Standard setting:
Description:
5 ↔ 40°C
21°C
Here the desired room temperature is set. This
setpoint can also be set on the front page of the the
control panel.
↳
Summer/winter mode switch (°C) Settings:
Standard setting:
Description:
5 ↔ 30°C
12°C
At the set temperature, the unit switches between
summer and winter mode.
In winter mode, the unit cannot cool when running in
Auto mode.
↳
Summer/winter mode offset (°C) Settings:
Standard setting:
Description:
0 ↔ 10°C
2°C
Here the offset temperature is set for switching
between summer and winter modes.
Example of summer/winter mode
Offset 2°C
Offset 2°C
12°C
The setpoint for switch between summer and winter modes is 12°C with an offset of 2°C, which means:
T
he unit switches to summer mode when outdoor temperatures are ˃ 14°C and to winter mode when
outdoor temperatures are ˂ 10°C.
22