Applications Releasing Applications
66 NFS-640 Installation Manual P/N 51332:B1 12/01/2003
4.5.6 Connecting an NBG-12LRA Agent Release-Abort
Station
Figure 41 Typical Connections for an NBG-12LRA Agent Release-Abort Station
Note: If using the on-board NACs, see Circuit Requirements for Section 4.5.4 “Connecting a
Releasing Device to the Control Panel” on page 64. If using FCM-1, see Circuit Requirements for
Section 4.5.5 “Connecting a Releasing Device to the FCM-1 Module” on page 65.
+
+
+
+
+
1
2
4
6
5
7 -
6 +
1
2
3
4
0
+
+
+
+
SLC loop to
FACP or LEM-320
FCM-1
FRM-1
FMM-1
FMM-101
Black
Red
Yellow
Violet
Black
Red
Yellow
Violet
Non-resettable +24 VDC
from main power supply
Manual Abort
Manual Release
Normal
Release
NBG-12LRA
See Document 51369
for installation details.
ELR mode R-47K
supervised and
power-limited
RedBrown
24 VDC UL-listed
releasing device
C.
N.O.
REL-47K
(use with Type Code
Rel Ckt ULC)
NBG640-NBG12LRA.cdr
System
Common (–)
24 VDC power
from FACP’s
main power supply
N.C.
Power Supervision
Relay A77-716B
N.C. Supervision
Relay Contact

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals