EasyManuals Logo
Home>Notifier>Fire Alarms>NFS-640

Notifier NFS-640 Installation Manual

Notifier NFS-640
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
Electrical Specifications Electrical Specifications
76 NFS-640 Installation Manual P/N 51332:B1 12/01/2003
Signaling Line Circuit (SLC)
Notification Appliance Circuits & Releasing Circuits
Output Relays
Output relays for Alarm, Trouble, Supervisory, and Security are available on power supply
terminals TB8, TB9, TB10, and TB11 respectively.
Contact ratings: 2.0 A @ 30 VDC (resistive)
Four-wire Smoke Detector Power
Control Panel terminals TB7 RESET (+) and (–) supply filtered, low-noise power for four-wire
smoke detectors. Specifications are:
Nominal voltage: 24 VDC
Maximum rated current: 1.25 A DC
Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible 24 VDC detectors.
Item Value
Voltage 24 VDC nominal, 27.6 VDC maximum
Maximum length 12,500 ft. (3810 m) per channel (NFPA Style 4) or 10,000 ft. (3048 m) total
loop or circuit length (NFPA Style 6 and 7)
Note: Refer to Appendix B.2 “Wire Requirements” for limitations.
Maximum current 400 mA peak, 200 mA average (max short circuit; circuit will shut down
until short is fixed)
Maximum resistance 50 ohms (supervised and power-limited)
Item Value
Max. wiring voltage
drop
2 VDC (except CMX which is 1.2 VDC)
Nominal operating
voltage
24 VDC
Current for all external
devices connected to
the control panel’s
power supply
6.0 A in alarm (3 A continuous)
Optional ACPS-2406 Total 6 A in alarm (5 A continuous)
Optional APS-6R Total 6 A in alarm (4 A continuous)
Maximum signaling
current/circuit per NAC
2.5 A
Note: Some devices have maximum draws less than this;
refer to the device’s documentation.
End-of-Line Resistors
(ELRs)
Control Panel NACs (TB3, TB4, TB5, TB6): 2.2K, 1/2 watt
ICM-4RK, ICE-4, VCM-4RK, VCE-4, and DCM-4RK: 4.7K,
1/2 watt (2 watts on 70 Vrms audio)
XP5-C, XP5-C, FCM-1 Modules: 47K, 1/2 watt

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals