E5@C Digital Temperature Controllers User’s Manual (H174)
6-7 Initial Setting Level
6
sl-h
SP Upper Limit
sl-l
SP Lower Limit
• These parameters set the upper and lower limits of the set points. A set point can be set
within the range defined by the upper and lower limit set values in the SP Upper Limit and
SP Lower Limit parameters. If these parameters are reset, any set point that is outside of
the new range will be forcibly changed to either the upper limit or the lower limit.
• When the temperature input type and temperature unit have been changed, the set point
upper limit and set point lower limit are forcibly changed to the upper and lower limits of
the sensor.
• For a temperature input, the decimal point position depends on the currently selected
sensor, and for an analog input it depends on the Decimal Point parameter setting.
Related Parameters
Input Type (Initial Setting Level): Page 6-43
Temperature Unit (Initial Setting Level): Page 6-44
cntl
PID ON/OFF A Standard Model must be used.
• This parameter selects 2-PID control or ON/OFF control.
• The auto-tuning and self-tuning functions can be used in 2-PID control.
Related Parameters
AT Execute/Cancel (Adjustment Level): Page 6-20
Manual Reset Value (Adjustment Level): Page 6-30
Hysteresis (Heating) and Hysteresis (Cooling) (Adjustment Level): Page 6-31
ST Stable Range (Advanced Function Setting Level): Page 6-67
Parameter name Setting range Unit Default
Set Point Upper
Limit
Temperature
input
SP lower limit + 1 to Input setting
range upper limit
EU 1300
Analog input SP lower limit + 1 to scaling upper
limit
EU 100
Set Point Lower
Limit
Temperature
input
Input setting range lower limit to
SP upper limit - 1
EU −200
Analog input Scaling lower limit to SP upper
limit - 1
EU 0
Setting range Default
pid: 2-PID, onof: ON/OFF onof