Communications Setting Level Section 5-8
5-8 Communications Setting Level
Each parameter is enabled when the power is reset.
Match the communications specifications of the E5@Z and the host com-
puter. If multiple devices are connected, ensure that the communications
specifications for all devices in the system (except the Communications
unit number) are the same.
Related Parameter
Communications writing (adjustment level): Page 108
psel Protocol Setting
Communications must be supported.
u-no Communications Unit No.
bps Communications Baud Rate
len Communications Data Length
CompoWay/F must be selected as the protocol.
sbit Communications Stop Bits
CompoWay/F must be selected as the protocol.
prty Communications Parity
sdwt Send Data Wait Time
Function
Setting
Item Symbol Set values Settings Default
Protocol setting psel cwf, mod CompoWay/F
(SYSWAY), Modbus
cwf
Communications Unit
No.
u-no 0 to 99 0 to 99 1
Communications baud
rate
bps 1.2, 2.4, 4.8, 9.6,
19.2, or 38.4 (kbps)
1.2, 2.4, 4.8, 9.6,
19.2, or 38.4 (kbps)
9.6
Communications data
length
len 7, 8 (bits) 7, 8 (bits) 7
Communications stop
bits
sbit 1, 2 1, 2 2
Communications parity prty none, even, odd None, Even, Odd even
Send data wait time sdwt 0 to 99 0 to 99 (ms) 20
See
See

Table of Contents

Other manuals for Omron E5CZ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CZ and is the answer not in the manual?

Omron E5CZ Specifications

General IconGeneral
BrandOmron
ModelE5CZ
CategoryTemperature Controller
LanguageEnglish

Related product manuals