Chapter 5
5-17
Troubleshooting
When using the Servo Driver under the continuous operation mode, cool the Servo Driver with fans
and air conditioners to maintain an ambient operating temperature below 40
°C.
The life of aluminum analytical capacitors is greatly affected by the ambient operating temperature.
Generally speaking, an increase of 10
°C in the ambient operating temperature will reduce capacitor
life by 50%. We recommend that ambient operating temperature be lowered and the power supply
time be reduced as much as possible to lengthen the maintenance times for Servo Drivers.
If the Servomotor or Servo Driver is not to be used for a long time, or if they are to be used under
conditions worse than those described above, a periodic inspection schedule of five years is recom-
mended. Please consult with OMRON to determine whether or not components need to be
replaced.