Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B English —
9.2.1 Customer menu
Use the Customer menu to correct or determine system-specific values. In the course of commissioning, the factory settings must be
adjusted for the system-specific conditions.
A three-digit PM code is assigned to the setting options
Language EN Display language
Date dd:MM:yy Date
005 Minimum working pressure P
0
1.8 bar
see chapter 7.2 "Determining the P
0
minimum operating
pressure for the controller" on page 29
006 Safety valve, pressure 3.0 bar
Tripping pressure for the safety valve at the heat
generator in the system
Degassing, active only in Fillcontrol Auto 2PS
011 Degassing programme Continuous degassing
Continuous degassing time 24 h
020 Maximum makeup time 20 minutes
021 Maximum makeup cycles 3 cycles within 2 hours 3x makeup within 2 hours for maximum 20 minutes each
Optional contact water meter
023 Makeup quantity 0 Litres Only if controller with "With water meter YES"
024 Maximum makeup quantity
Next maintenance 18 months Time left to the next due maintenance
Floating alarm contact NO Only the messages marked in the "Messages" list
Horn NO Acoustic signal is output with the fault contact
Fault memory History of all messages
Parameter memory History of parameter input
Software version V0.60