9.3 Messages
Messages with ER codes are displayed at the controller.
Use the arrow keys at the controller operating panel to select the messages.
By selecting the "Fault memory" main menu in the Customer menu, you display the last 20 alarms.
Alarm causes can be eliminated by the operator or a specialist workshop.
If required, please contact the Reflex Customer Service.
Note!
Clearing of the cause must be confirmed by pressing the “Ack” button on the operator panel. All other alarms are
automatically reset as soon as the cause has been eliminated.
Note!
Floating contacts, setting in the Customer menu, see chapter
7.5 "Parametrising the controller in the Customer menu" on
page
31 .
ER Code
Alarm
Floating
contact
Cause
Remedy
Alarm reset
01 Minimum pressure Yes Set value not reached
Water loss in the system
Pump fault
Expansion tank defective
Check set value in the
Customer or Service
menu
Check water level
Check pump
Check expansion tank
-
02.1 Insufficient water -
Insufficient water switch has
actuated for too long
Open the degassing line
Clean the dirt trap
Replace the degassing
valve
Quit
02.2 Insufficient water -
Insufficient water switch
triggered
Check the supply line
from the fresh-water
system to the system
separator tank
Check the function of
the float valve in the
system separator tank
Quit
04.1
04.2
Pump1
Pump2
Yes Pumps disabled
Pumps jammed
Pump motor defective
Pump motor protector
(Klixon) tripped
Fuse defective
Rotate the pumps with
screwdriver
Replace the pump
motor
Electrically test the
pump motor
Replace the 10 A fuse
Quit
06 Makeup time - Set value exceeded
Water loss in the system
Makeup line not connected
Makeup rate insufficient
Makeup hysteresis too low
Check set value in the
Customer or Service
menu
Check water level
Connect makeup line
Quit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reflex Fillcontrol Auto Series and is the answer not in the manual?

Reflex Fillcontrol Auto Series Specifications

General IconGeneral
BrandReflex
ModelFillcontrol Auto Series
CategoryService Equipment
LanguageEnglish

Related product manuals