Description of the device
Fillcontrol Auto Make-up and degassing06.07.2016 - Rev. B English
13
4.4.2 Fillcontrol Auto 2PS
1 Vacuum gauge 10 Vacuum spray tube
2 Motor ball valve 11 Ball valve
3 Connection of degassing line with dirt trap 12 Pressure sensor
4 Automatic quick venting unit 13 Pump
5 Operating unit 14 Pump
6 Main switch 15 System connection
7 Control cabinet 16 Insufficient water switch
8 Drainage cock 17 Connection, fresh-water system with dirt trap
9 System separator vessel
The pressure transducer sends a signal to the controller if the pressure drops below the filling pressure of the plant system. The
controller activates the pumps. Water from the vacuum spray pipe is added to the plant system. The motor ball valve regulates the water
inflow into the vacuum spray pipe. Either gas-enriched water from the plant system is degassed in the vacuum spray pipe or water from
the system separator tank is added to the vacuum spray pipe. The float valve in the system separator tank ensures a water supply from
the makeup system.
To prevent potential dry-running, the integrated insufficient water protection unit in the system separator tank and the vacuum spray
pipe will shut down the pumps, if required.
The device controller monitors water degassing and makeup in the plant system. These functions are monitored by the controller:
Makeup time
Makeup cycles
Makeup quantity
Degassing
Continuous degassing
Interval degassing
The controller interrupts the makeup when the set makeup time or the number of makeup cycles is exceeded. Small leaks in the plant
system are detected in this way.
The makeup quantity is controlled by the controller if an optional "FQIRA+" water meter is installed. For the optional water meter, see
chapter 4.6 "Optional equipment and accessories" on page 15 .

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reflex Fillcontrol Auto Series and is the answer not in the manual?

Reflex Fillcontrol Auto Series Specifications

General IconGeneral
BrandReflex
ModelFillcontrol Auto Series
CategoryService Equipment
LanguageEnglish

Related product manuals