Rockwell Automation Publication 520-UM001I-EN-E - July 2016 111
Programming and Parameters Chapter 3
Advanced Display Group (continued)
d368 [Testpoint Data] Related Parameter(s): A483
Displays the present value of the function selected in A483 [Testpoint Sel].
Values Default: Read Only
Min/Max: 0/FFFF
Display: 1
d369 [Motor OL Level]
Displays the motor overload counter.
Values Default: Read Only
Min/Max: 0.0/150.0%
Display: 0.1%
d375 [Slip Hz Meter] Related Parameter(s): P032
Displays the current amount of slip or droop (absolute value) being applied to the motor frequency. Drives applies slip based on the setting for P032 [Motor NP Hertz].
Values Default: Read Only
Min/Max: 0.0/25.0 Hz
Display: 0.1 Hz
d376 [Speed Feedback]
32 bit parameter.
Displays the value of the actual motor speed whether measured by encoder/pulse train feedback or estimated.
Values Default: Read Only
Min/Max: 0.0/64000.0 rpm
Display: 0.1 rpm
d378 [Encoder Speed]
32 bit parameter.
Provides a monitoring point that reflects the speed measured from the feedback device. This shows the encoder or pulse train speed even if not used directly to control motor speed.
(1)
Values Default: Read Only
Min/Max: 0.0/64000.0 rpm
Display: 0.1 rpm
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later.
d380 [DC Bus Ripple]
Displays the real-time value of the DC bus ripple voltage.
Values Default: Read Only
Min/Max: 0/410VDC for 230V AC drives; 820VDC for 460VAC drives; 1025VDC for 600VAC drives
Display: 1V DC
d381 [Output Powr Fctr]
Displays the angle in electrical degrees between motor voltage and motor current.
Values Default: Read Only
Min/Max: 0.0/180.0 deg
Display: 0.1 deg