212 Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Appendix D Velocity StepLogic, Basic Logic and Timer/Counter Functions
The timer function is used to select a preset speed with a 20 second run
time that overrides the speed reference while the digital input is active.
Parameters are set to the following options:
P047 [Speed Reference1] = 6 “4-20mA Input”
P049 [Speed Reference2] = 7 “Preset Freq”
t062 [DigIn TermBlk 02] = 1 “Speed Ref 2”
t063 [DigIn TermBlk 03] = 19 “Timer Start”
t076 [Relay Out1 Sel] = 25 “Timer Out”
t077 [Relay Out1 Level] = 20.0 Secs
A411 [Preset Freq 1] = 30.0 Hz
The control terminal block is wired such that a start command will also
trigger the timer start.
The relay output is wired to I/O Terminal 02 (DigIn TermBlk 02) so that
it forces the input on when the timer starts.
After the timer is complete, the output is turned off releasing the preset
speed command. The drive defaults to following the analog input
reference as programmed.
Note that a “Reset Timer” input is not required for this example since the “Timer
Start” input both clears and starts the timer.
Counter Function
Digital inputs and outputs control the counter function and are configured with
parameters t062...t063, t065...t068 [DigIn TermBlk xx] set to 20 “Counter In
and 22 “Reset Countr.
Digital outputs (relay and opto type) define a preset level and indicate when the
level is reached. Level parameters t077 [Relay Out1 Level], t082[Relay Out2
Level], t070 [Opto Out1 Level] and t073 [Opto Out2 Level] are used to set the
desired count value.
Parameters t076 [Relay Out1 Sel], t081 [Relay Out2 Sel], t069 [Opto Out1 Sel]
and t072 [Opto Out2 Sel] are set to 26 “Counter Out” which causes the output
to change state when the level is reached.
Example
A photo eye is used to count packages on a conveyor line.
An accumulator holds the packages until 5 are collected.
A diverter arm redirects the group of 5 packages to a bundling area.
The diverter arm returns to its original position and triggers a limit switch
that resets the counter.
Parameters are set to the following options:
t065 [DigIn TermBlk 05] = 20 “Counter In
t066 [DigIn TermBlk 06] = 22 “Reset Countr
t076 [Relay Out1 Sel] = 26 “Counter Out”
t077 [Relay Out1 Level] = 5.0 Counts

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation B Series and is the answer not in the manual?

Rockwell Automation B Series Specifications

General IconGeneral
BrandRockwell Automation
ModelB Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals