Rockwell Automation Publication 520-UM001I-EN-E - July 2016 141
Programming and Parameters Chapter 3
Advanced Program Group (continued)
Network Parameter Group
This group contains parameters for the network option card that is installed.
Refer to the network option card’s user manual for more information on the
available parameters.
A585 [PM Stable Brk Pt]
PowerFlex 525 only.
(With FRN 5.xxx and later.)
Percentage of rated power P037 [Motor NP Power] for the gain of (A584 [PM Stable 2 Kp] x A583 [PM Stable 1 Kp]).
Values Default: 40%
Min/Max: 0/100%
Display: 1%
A586 [PM Stepload Kp]
PowerFlex 525 only.
(With FRN 5.xxx and later.)
The gain to ensure robustness under step load in low speed region.
Values Default: 0%
Min/Max: 0/1000%
Display: 1%
A587 [PM 1 Efficiency]
PowerFlex 525 only.
(With FRN 5.xxx and later.)
Reduce full load current.
Values Default: 120%
Min/Max: 0/2000%
Display: 1%
A588 [PM 2 Efficiency]
PowerFlex 525 only.
(With FRN 5.xxx and later.)
Reduce no load current.
Values Default: 500%
Min/Max: 0/2000%
Display: 1%
A589 [PM Algor Sel] Related Parameter(s): A550
Stop drive before changing this parameter.
PowerFlex 525 only.
(With FRN 5.xxx and later.)
Selects the algorithm to use with your motor. Check with the manufacturer of your motor to determine whether it is an iPM or sPM motor.
Options 0 “Algorithm 1” (Default) Suggested for most motors.
1 “Algorithm 2” Enable an embedded algorithm to reduce oscillation in output waveform (use with sPM motor only, do not enable for iPM motor).