168 Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Appendix A Supplemental Drive Information
Environmental Specifications
AC 156 Tested by Trentec to be compliant with AC156 Acceptance Criteria for Seismic Qualification
Testing of Nonstructural Components and 2003 International Building Code for worst-case
seismic level for USA excluding site class F
SEMI F47 Electric Power Research Institute
Certified compliant with the following standards:
SEMI F47
IEC 61000-4-11
IEC 61000-4-34
Lloyds Register (Applicable to PowerFlex 525 drives only)
Lloyd’s Register Type Approval Certificate 12/10068(E1)
RoHS Compliant with the European “Restriction of Hazardous Substances” Directive
The drive is also designed to meet the appropriate portions of the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 7.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable
Speed Drive Systems.
Certifications PowerFlex 523 PowerFlex 525
Specifications PowerFlex 523 PowerFlex 525
Altitude:
Without derating:
With derating:
See Current Derating Curves
on page 17 for derating guidelines.
1000 m (3300 ft) max.
Up to 4000 m (13,200 ft) max., with the exception of 600V drives at 2000 m (6600 ft)
max.
Max. Surrounding Air
Temp er atu re
Without derating:
With derating:
See Current Derating Curves
on page 17 for derating guidelines.
-20...50 °C (-4...122 °F)
-20...60 °C (-4...140 °F) or -20...70 °C (-4...158 °F) with optional Control Module Fan
kit.
Storage Temperature:
Frame A...D:
Frame E:
-40...85 °C (-40...185 °F)
-40...70 °C (-40...158 °F)
Atmosphere:
Relative Humidity: 0...95% noncondensing
Shock:
Vibration:
Complies with IEC 60068-2-27
Complies with IEC 60068-2-6:1995
Drive must not be installed in an area where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must
be stored in an area where it will not be exposed to a corrosive atmosphere.
Frame
Size
Operating and Nonoperating Nonoperating (Transportation)
Force
(Shock/Vibration) Mounting Type
Force
(Shock/Vibration) Mounting Type
A 15 g / 2 g DIN rail or screw 30 g/ 2.5 g Screw only
B 15 g / 2 g DIN rail or screw 30 g/ 2.5 g Screw only
C 15 g / 2 g DIN rail or screw 30 g/ 2.5 g Screw only
D 15 g / 2 g Screw only 30 g/ 2.5 g Screw only
E 15 g / 1.5 g Screw only 30 g/ 2.5 g Screw only